קטלוג מוצרים ULPA - AAF

AstroCel® TM Disposable Ceiling Module Specifications Note : 1) Standard inlet collar is ø250mm (10"). 2) Other sizes and specifications are available upon request. (Maximum size 610mm x 1220mm) 3) Recommended final resistance : 1.6" W.G./400Pa. 4) Add 15 Pa to initial resistance for Module Construction. 5) Add 50mm(1.97") for collar height. Product Information Size in mm Nominal Airflow @ 0.45 m/s Initial Resistance @ 0.45 m/s H13 (HEPA) A B C (m3/h) (m3/s) (In. W.G.) (Pa) (In. W.G.) (Pa) 600 600 600 600 600 600 600 915 1210 600 915 1210 152 152 152 175 175 175 600 900 1200 600 900 1200 0.166 0.250 0.333 0.166 0.250 0.333 0.50 0.50 0.50 0.32 0.32 0.32 125 125 125 80 80 80 0.58 0.58 0.58 0.36 0.36 0.36 145 145 145 90 90 90 U15 (ULPA) AAF has a policy of continuous product research and improvement and reserves the right to change design and specifications without notice. CR-ASTTM-03-SIN/0105 A-A View Isometric View Standard Operating Temperature : 70˚C (158˚F) Housing : Anodized aluminum extrusion, standard profile Gasket : No gasket Faceguard Location : Air leaving side Media : H13 HEPA Filter (99.99% efficiency on 0.3 μm particles) Options : U15 ULPA Filter (99.9995% efficiency on 0.12 μm particles) Flat profile, closed cell neoprene gasket on air leaving side Eliminate faceguard Divider and volume control damper Adjustable distribution plate with divider 300mm (12") inlet collar CERT. NO. 6396 REG. NO. 1599 ISO 9001 : 2000 Certified INTERNATIONAL CERTIFICATION 014 ISO/IEC GUIDE 62 : 1996 QS 10082001 CB 02 www.aafasia.com

RkJQdWJsaXNoZXIy MjgzNzA=