DriPak 2000 Specifications 66℃ Synthetic fiber Sealant and thermoplastic 3 Up to 3400m /h Galvanized steel, stainless steel, plastic Maximum Operating temperature Media Pocket Protector Rated Volume Frame : : : : : Initial Resistance vs Airflow Capacity Efficiency vs Particle Size Initial Resistance(Pa) Rated Air Velocity(%) Efficiency(%) Particle size(μm) 0 25 50 75 100 125 50 75 100 125 150 0.1 1 10 10 20 30 40 50 60 70 80 90 100 0.4 375 or 2-3 times of initial resistance Product Specification (1) ; (2) 。 The filter is available under 67% to133% rated face velocity All the data above is AAF test room data Notes: Size mm W×H×D Pockets Per Filter Rated Air Volume 3 (m /h) 2.5m/s 90-95% Rated Initial Resistance(Pa) 80-85% 60-65% 594×594×914 594×594×914 492×594×914 492×594×914 289×594×914 289×594×914 594×594×762 594×594×762 594×594×762 492×594×762 492×594×762 289×594×762 289×594×762 594×594×534 594×594×534 594×594×534 492×594×534 289×594×534 289×594×534 594×594×381 289×594×381 8 6 6 5 4 3 10 8 6 6 5 4 3 6 3 10 8 6 6 4 3 3400 3400 2848 2848 1700 1700 3400 3400 3400 2848 2848 1700 1700 3400 1700 3400 3400 3400 2848 1700 1700 80 87 90 90 95 87 90 190 190 135 140 145 145 140 145 67 70 75 75 80 70 75 138 138 110 115 120 120 115 120 59 65 70 59 65 65 66 71 76 66 71 71 55 65 60 60 65 65 60 86 86 90 95 100 100 95 100 51 55 60 51 55 55 Gross Media Area (㎡) 9.9 7.9 5.9 5.9 4.9 4.0 3.0 3.0 1.5 7.0 5.6 4.2 4.2 2.8 2.1 9.7 7.2 6.0 4.8 3.6 7.2 Recommended Final Resistance (Pa) 375 or 2-3 times of initial resistance 375 or 2-3 times of initial resistance 375 or 2-3 times of initial resistance