4/7 Dimensions Why should you focus on your ISO 8573-1 specifications? Certain industries like the pharmaceutical and food industry requires high-quality compressed air. By meeting the ISO 8573-1 standard requirements you can: Prevent production downtime: Processes and machines are stopped to find and eliminate the contamination issues. Ensure Process and Product Safety: Potential incidents, like contaminants meeting food via water and oil, can create safety concerns and unreliable processes. Avoid Production Failures and Poor Quality Finishes: Contaminants mixing with applications effect product results. Class Particle Concentration Pressure Dew Point Oil Concentration cn/m3 ºC (ºF) mg/m3 0.1 < d ≤ 0.5 µm 0.5 < d ≤ 1.0 µm 1.0 < d ≤ 5.0 µm 0 As specified by the equipment user or supplier and more stringent than class 1 1 ≤ 20,000 ≤ 400 ≤ 10 ≤ -70 (94.0) ≤ 0.01 2 ≤ 400,000 ≤ 6,000 ≤ 100 ≤ -40 (-40.0) ≤ 0.1 3 not specified ≤ 90,000 ≤ 1,000 ≤ -20 (-4.0) ≤ 1 4 not specified not specified ≤ 10,000 ≤ +3 (+37.4) ≤ 5 5 not specified not specified ≤ 100,000 ≤ +7 (+45.6) > 5 6 x x x ≤ +10 (+50.0) x ISO 8573-1:2010 is the main publication of the ISO 8573 series of standards, because it contains the permissible amount of contaminants per cubic meter of compressed air is fixed. ISO 8573-1 Compressed Air Classes S600 Compressed Air Purity Analyzer 364mm 180mm 470mm